Black Friday shopping list from the shop….. put a fire extinguisher at the top. Look around any boat shop in the winter. There's a pile of cedar shavings under the bench, a shelf of thinner, acetone and varnish, a heater running because it's November in Marblehead, and oily rags if you got lazy. That's everything a fire needs. Most of us own an extinguisher. Plenty of them are sitting on the floor behind the lumber rack, gauge in the red, older than the truck. Here's how I pick one, where I hang it, and how to use it if the day ever comes.
Why it matters: NFPA says the number one priority is getting out safely, and an extinguisher is one piece of a fire plan, not the whole plan. What it can do is knock down a small fire, a wastebasket or a smoldering rag, before it turns into a big one, or hold it until the fire department gets there. That only works if it's the right kind, it's charged, and you can grab it on your way to the door. A home-size extinguisher is empty in about 8 to 10 seconds, so you don't get a second try.
Materials:
- A UL-listed multipurpose (ABC) dry chemical extinguisher, 2-A:10-B:C at the very least. In a shop I'd step up to a 5 lb 3-A:40-B:C unit
- A second one for a bigger shop or a second floor, so none of them is more than about 40 ft from the next
- The wall bracket it came with (or a listed bracket), plus lag screws into a stud
- An inspection tag or a strip of masking tape and a marker for the monthly date
- For cleanup, if you ever use it: baking soda, a bucket, rags, an N95 and gloves
Tools: drill/driver, stud finder, tape measure, level, and a HEPA vac for the mess afterward.
The steps:
- Get the right letters. A shop has every kind of fire in it. Class A is wood, paper and cloth, so your shavings and dust. Class B is flammable liquids, like thinner, acetone, oil-based paint and varnish. Class C is energized electrical equipment, so your saws and that space heater. A multipurpose ABC extinguisher covers all three, and the U.S. Fire Administration says that's what most home stores carry. Make sure it carries a UL or ULC listing.
- Read the numbers. The label reads like 3-A:40-B:C. OSHA and the U.S. Fire Administration explain it. Each unit in front of the A is worth 1.25 gallons of water, so 3-A is about 3.75 gallons' worth and 2-A is 2.5. The number in front of the B is about how many square feet of burning liquid a regular person should be able to put out, so 40-B is about 40 sq ft. The C has no number. It just means the stuff won't carry current back to you. Kidde recommends a 2-A:10-B:C on every level of the house, garage and workshop included, no more than 40 ft apart. USFA says to buy the biggest one you can handle comfortably. A Kidde Pro 5 MP is rated 3-A:40-B:C, weighs about 9 lb, sprays 12 to 18 ft, and keeps going 13 to 15 seconds. That's real time for a shop fire, and it's rechargeable.
- Hang it on the way out. NFPA says to put extinguishers close to an exit, so you're backing toward the door while you fight the fire, not running deeper into the shop to get it. The Red Cross adds: away from heat sources. Don't hang it over the solvent shelf or next to the heater, where you'd have to reach into the fire to get it. NFPA 10 wants them along the normal path of travel, including exits, and in a bracket, not on the floor. On the plan, the extinguisher by the man door is a 32 ft walk from the finishing shelf and the one by the overhead door is 22 ft. In a shop with employees, OSHA limits the walk to 75 ft for Class A fires and 50 ft from a flammable-liquid area. In a home shop, the closer the better.
- Mount it at the right height. NFPA 10: anything 40 lb or less gets mounted with the top no higher than 5 ft (60 in) off the floor. Over 40 lb, 3-1/2 ft. Either way, the bottom has to be at least 4 in off the floor. I hang mine with the top at about 48 in, lagged into a stud, label facing out. Anyone in the house can reach that, and it's high enough that a sheet of plywood can't get leaned against it.
- Decide before you fight it. USFA's checklist: everyone's out or getting out, someone's called 911, the fire is small and stuck to one object or surface, you're clear of the smoke, and you've got a way out behind you. If any answer is no, get out and call 911. Portland Fire says to start 6 to 8 ft back with your back to the exit.
- PASS. Pull the pin, nozzle pointed away from you. That breaks the tamper seal. Aim low, at the base of the fire, not the flames. Squeeze the lever slowly and evenly. Kidde warns it may flare up for a second when it first hits. That's normal. Sweep side to side at the base, moving in carefully, until it looks out. Then back off and watch it. OSHA says if it flares up again, do it again. If it isn't dying down right away, or the extinguisher runs dry, leave and shut the door behind you. Even if you get it out, have the fire department look it over.
- Check it once a month. Kidde's manual says inspect it at least every 31 days. Make sure you can see it and get to it, and it's still on its bracket with the label facing out. The pin and tamper seal should be in place and the gauge needle in the green. Check that the nozzle is clear and there are no dents, leaks or corrosion. Heft it against the weight on the label, then initial and date the tag. In a salt-air shop, look hard at the corrosion. USFA notes some extinguishers need to be shaken monthly, so go by your label.
- Know when it's done. A disposable (non-rechargeable) extinguisher is out of service 12 years after the date stamped on the cylinder, no matter what the gauge says. Kidde says a disposable is finished after any use, even a short squirt, because even a momentary discharge lets it leak down. A rechargeable gets emptied and serviced every 6 years and pressure-tested at 12 (OSHA 1910.157). That's a job for a service shop, and so is recharging after use.
- Clean up the powder fast. ABC powder is monoammonium phosphate. Pyro-Chem's cleanup guide says it turns mildly acidic once it picks up moisture, and it can corrode metal and dull paint. Once the fire is out and cool, put on an N95 and gloves. HEPA-vacuum the loose powder. Then wash with 1 cup of baking soda in 3 gallons of hot water, let it sit a few minutes, rinse and dry. Unplug any tool before cleaning it. Clean the cast-iron saw and jointer tops the same day and wax them, or a damp Marblehead morning will rust every spot the powder touched.
MOAM's shop note: The extinguisher's job is to buy you time to get to the door, not to save the shop. Hang it by the door you'd actually run out of, not the one that looks nice. And on Black Friday, check the date on the bottom of the one you already have. A lot of the "spare" extinguishers in garages around here were made when the Patriots still played at Foxboro Stadium.
MOAM Out.
Sources: NFPA, "Fire extinguishers" (escape first, when to use one, PASS, multipurpose, labeled by a testing lab, mount near an exit) and "Fire Extinguisher Location and Placement" fact sheet (NFPA 10 mounting heights); NFPA 10 second draft report (6.1.3 placement along paths of travel and exits, brackets, 6.1.3.9 installation height); U.S. Fire Administration, "Choosing and Using Fire Extinguishers" (classes, ABC, UL label, biggest you can handle, rating numbers, checklist, PASS, maintenance); OSHA, 29 CFR 1910.157 (75 ft Class A and 50 ft Class B travel distance, monthly inspection, annual maintenance, 6-year maintenance and 12-year hydrostatic test) and eTool: Fire Extinguisher Use (PASS, pin breaks the tamper seal, back away, evacuate if it isn't working); Kidde, "How to Use Your Kidde Fire Extinguisher" (PASS, brief flare-up, 2-A:10-B:C on every level, no more than 40 ft apart), Pro 5 MP specifications (3-A:40-B:C, 9.0 lb, 4.5 x 16.31 in, 12 to 18 ft range, 13 to 15 seconds, rechargeable), "How to Tell When You Need to Refill Your Fire Extinguisher" (gauge in the green and under 12 years old) and disposable dry chemical owner's manual (31-day inspection checklist, replace after any use, 12-year maximum life); Portland Fire & Rescue, "Portable Fire Extinguisher Guide" (6 to 8 ft back, 8 to 10 seconds, 6 to 10 ft range); American Red Cross, "Fire Safety Equipment" (ABC for home, near an exit, away from heat, get out if it doesn't die down); Pyro-Chem, "Dry Chemical Clean-Up Procedures" (monoammonium phosphate mildly acidic with moisture, HEPA vacuum, 1 cup baking soda per 3 gallons hot water, shut off electrical equipment first); Eastern Oregon University EH&S, "Cleanup of ABC (Dry Chemical) Fire Extinguisher Discharges" (gloves, goggles and an N95 for cleanup, corrosive to metal, clean metal first).